CIESC Journal

• 传递现象 • 上一篇    下一篇

采用R407C的热泵系统工质非完全相变及其对系统参数的影响

赵力   

  1. 天津大学机械工程学院热能系,天津 300072

  • 出版日期:2005-05-25 发布日期:2005-05-25

R407C Incomplete phase changing in heat pumps and its influence on system parameters

ZHAO Li   

  • Online:2005-05-25 Published:2005-05-25

摘要: 为了揭示热泵系统中R407C在冷凝器和蒸发器中非完全相变与系统参数的关系,首先引出了换热流体极限流量的概念,然后利用热力学循环分析的方法对R407C的非完全相变现象进行了研究,给出了影响R407C非完全相变的几种主要系统参数,如工质与换热流体之间的温差以及压缩机的排气量等,并给出了这些参数与换热流体极限流量之间的定性关系,最后又讨论了换热器内部工质的压降对该工质非完全相变的影响.

Abstract: In order to reveal some relationships between system parameters and R407C incomplete phase changing in condenser and evaporator, a concept is presented firstly, that is the maximum flow rate of heat-transfer fluids. Afterwards thermodynamics cycle analyzing is used, and some important system parameters are given, such as temperature difference between R407C and heat-transfer fluids, compressor discharge capacity. These parameters can affect on the maximum flow rate of heat-transfer fluids, and the results are shown in some figures. Lastly, relationship is discussed too between R407C’s pressure drop in condenser or evaporator and the incomplete phase change.