CIESC Journal

• 能源和环境工程 • 上一篇    下一篇

运行工况对双效空冷吸收式制冷循环性能的影响

陈焕新;尚瑞;舒朝晖;谢军龙   

  1. 华中科技大学能源与动力工程学院,湖北 武汉 430074

  • 出版日期:2008-12-30 发布日期:2008-12-30

Effects of different operating conditions on cycle performance of double-effect air-cooled absorption refrigeration

陈焕新;尚瑞;舒朝晖;谢军龙

  

  • Online:2008-12-30 Published:2008-12-30

摘要:

采用空冷吸收器、空冷冷凝器实现循环空冷化,是缩小吸收式系统体积、扩大其应用领域的重要途径之一。针对4种空冷双效溴化锂循环,建立集中参数模型,分析比较了不同运行参数(热源温度、室外冷却空气温度、蒸发温度)对4种循环性能的影响情况。结果表明,要实现循环空冷化,必须提高热源温度,同时4种循环相比,溶液在低温溶液热交换器前分流的并联循环热力性能明显低于其他3种循环,不宜空冷化。

Abstract:

Air-cooled absorber and condenser is one of the most significant methods to reduce the bulk volume of absorption refrigeration system and to extend its range of application.In this paper,lumped parameter model for four double-effect air-cooled lithium bromide absorption refrigeration cycles was developed to analyze effects of varying heat reservoir temperature,cooling air temperature and evaporation temperature on system performance.The simulated result indicated that increased temperature of heat reservoir is essential to the air-cooled absorption system,and coefficient of performance of the cycle with parallel solution flow in which solution flow is distributed prior to low temperature solution heat exchanger is much lower than that of the other three cycles,thereby is unfit for absorber and condenser to be air cooled.