Chinese Journal of Chemical Engineering ›› 2012, Vol. 20 ›› Issue (4): 710-714.

• 过程系统工程 • 上一篇    下一篇

基于绝热加速量热测试的过氧化叔丁基反应失控的泄放设计

魏彤彤, 蒋慧灵   

  1. Department of Fire Protection Engineering, Chinese People’s Armed Police Force Academy, Langfang 065000, China
  • 收稿日期:2011-03-08 修回日期:2011-09-20 出版日期:2012-08-28 发布日期:2011-09-20

Venting design for di-tert-butyl peroxide runaway reaction based on accelerating rate calorimeter test

WEI Tongtong; JIANG Huiling   

  1. Department of Fire Protection Engineering, Chinese People’s Armed Police Force Academy, Langfang 065000, China
  • Received:2011-03-08 Revised:2011-09-20 Online:2012-08-28 Published:2011-09-20

摘要: In order to design the relief system size of di-tert-butyl peroxide (DTBP) storage tanks, the runaway reaction of DTBP was simulated by accelerating rate calorimeter (ARC). The results indicated that under adiabatic conditions the initial exothermic temperature was 102.6 ?C, the maximum self-heating rate was 3.095×107 ?C•min?1, the maximum self-heating temperature was 375.9 ?C, and the pressure produced by unit mass was 4.512 MPa•g?1. Judged by ARC test, the emergency relief system for DTBP was a hybrid system. Based on Design Institute for Emergency Relief System (DIERS) method, the releasing mass flow rate W was determined by Leung methods, and the mass velocity G was calculated by two modified Omega methods. The two relief sizes calculated by monograph Omega method and arithmetic Omega method are close, with only 0.63% relative error. The monograph Omega method is more convenient to apply.

关键词: di-tert-butyl peroxide, accelerating rate calorimeter, runaway reaction, venting size

Abstract: In order to design the relief system size of di-tert-butyl peroxide (DTBP) storage tanks, the runaway reaction of DTBP was simulated by accelerating rate calorimeter (ARC). The results indicated that under adiabatic conditions the initial exothermic temperature was 102.6 ?C, the maximum self-heating rate was 3.095×107 ?C•min?1, the maximum self-heating temperature was 375.9 ?C, and the pressure produced by unit mass was 4.512 MPa•g?1. Judged by ARC test, the emergency relief system for DTBP was a hybrid system. Based on Design Institute for Emergency Relief System (DIERS) method, the releasing mass flow rate W was determined by Leung methods, and the mass velocity G was calculated by two modified Omega methods. The two relief sizes calculated by monograph Omega method and arithmetic Omega method are close, with only 0.63% relative error. The monograph Omega method is more convenient to apply.

Key words: di-tert-butyl peroxide, accelerating rate calorimeter, runaway reaction, venting size