• 流体力学与传递现象 • Previous Articles Next Articles
ZHENG Keqing,ZHANG Xuejun,TIAN Xinjian,QIU Limin
Online:
Published:
郑克晴,张学军,田新建,邱利民
Abstract:
Ice slurry generator is a key equipment in the direct contact ice slurry making process.As an important assessment parameter of the ice slurry generator performance,the volumetric heat transfer coefficient is greatly affected by many factors.In this paper,qualitative analysis of various effects on the volumetric heat transfer coefficient is done,based on the rising characteristics of a single bubble in the continuous phase.The experimental results show that the decrease of the water column height,the inlet air temperature,and the nozzle diameter,as well as the increase of the air mass flow rate,will lead to an increase of the volumetric heat transfer coefficient.
摘要:
冰浆生成器是直接接触法冰浆制取系统的关键设备之一,而体积传热系数作为衡量冰浆生成器性能的重要参数受诸多因素影响。基于单个气泡在连续相中的上升特性,定性分析了各种因素对体积传热系数的影响。实验结果表明:进气温度下降、进气质量流量增加、水柱高度下降、喷嘴直径减小均导致体积传热系数增加。
ZHENG Keqing,ZHANG Xuejun,TIAN Xinjian,QIU Limin. Heat transfer performance of a single air bubble in direct contact ice slurry generator[J]. .
郑克晴,张学军,田新建,邱利民. 直接接触式冰浆生成器的单气泡传热特性 [J]. CIESC Journal.
Add to citation manager EndNote|Ris|BibTeX
URL: https://hgxb.cip.com.cn/EN/
https://hgxb.cip.com.cn/EN/Y2010/V61/IS2/58