Abstract:

This paper presents a novel experimental and analytical waste heat recovery and dehumidification system on the recovery of waste heat from data centers. The proposed system uses desiccant-coated heat exchangers to harvest waste heat and utilize it for the dehumidification of fresh air, thus enabling local consumption of the recovered waste heat. The study focuses on a liquid-cooled data center at a research institute in Shanghai as the experimental subject. The performance of the waste heat recovery and dehumidification system was evaluated through a series of tests. Results show that the system is capable of recovering waste heat at 50℃ from the liquid-cooled data center to continuously dehumidify fresh air. The average coefficient of performance (COP) for dehumidification reaches 8.85. Furthermore, at an airflow rate of 4500 m³/h and a dehumidification duration time of 6 minutes, the average waste heat recovery efficiency achieves 41.94%.

Key words: data center waste heat recovery, desiccant-coated heat exchanger, adsorption, regeneration, experimental validation

摘要:

提出一种新型数据中心余热回收系统实验与分析,利用除湿换热器回收数据中心余热进行新风除湿,实现数据中心余热就地消纳。以上海某研究所冷板式液冷数据机房为研究对象,试制余热回收除湿系统进行除湿性能及余热回收性能的测试。实验结果表明,采用除湿换热器回收冷板式液冷数据机房的50℃余热对新风进行连续除湿,平均除湿性能系数(COP)最高可达8.85,在6 min、4500 m3/h工况下平均余热回收效率可达41.94%。

关键词: 数据中心余热回收, 除湿换热器, 吸附, 再生, 实验验证