化工学报 ›› 2014, Vol. 65 ›› Issue (4): 1221-1228.DOI: 10.3969/j.issn.0438-1157.2014.04.010

• 流体力学与传递现象 • 上一篇    下一篇

HFC134a水平二维与三维肋管外冷凝换热特性

马志先1,2, 张吉礼1, 孙德兴2, 周浩平3   

  1. 1 大连理工大学土木学院, 辽宁 大连 110064;
    2 哈尔滨工业大学市政环境工程学院, 黑龙江 哈尔滨 150090;
    3 江苏萃隆精密铜管股份有限公司, 江苏 常熟 215562
  • 收稿日期:2013-08-19 修回日期:2013-12-31 出版日期:2014-04-05 发布日期:2014-01-10
  • 通讯作者: 张吉礼
  • 作者简介:马志先(1982—),男,博士后。
  • 基金资助:

    国家自然科学基金项目(51078053);“十二五”国家科技部支撑计划项目(2011BAJ03B12-3):中国博士后科学基金项目:中央高校基本科研业务费项目(DUT12RC(3)81)。

Film condensation characteristics of HFC134a on enhanced horizontal tubes with two dimensional and three dimensional integral fins

MA Zhixian1,2, ZHANG Jili1, SUN Dexing2, ZHOU Haoping3   

  1. 1 School of Civil Engineering, Dalian University of Technology, Dalian 116024, Liaoning, China;
    2 School of Municipal and Environment Engineering, Harbin Institute of Technology, Harbin 150090, Heilongjiang, China;
    3 Jiangsu Cuilong Precision Copper Tube Corporation, Changshu 215562, Jiangsu, China
  • Received:2013-08-19 Revised:2013-12-31 Online:2014-04-05 Published:2014-01-10
  • Supported by:

    supported by the National Natural Science Foundation of China(51078053),the National Science & Technology Pillar Program during the Twelfth Five-year Plan Period of China(2011BAJ03B12-3), China Postdoctoral Science Foundation Funded Project and the Fundamental Research Funds for the Central Universities(DUT12RC(3)81).

摘要: 环保工质与高效冷凝管的应用对制冷行业实现节能减排意义重大,工质在强化管外膜状凝结换热特性是二者推广应用的关键。建立了水平管外膜状凝结换热试验系统,研究了HFC134a在4种二维肋管与2种三维肋管外的膜状凝结传热特性。试验管公称外径为19.05 mm、有效换热长度为1000 mm;试验中,通过改进的Wilson图解法获取试验管水侧对流传热系数。结果表明: HFC134a水平二维与三维肋管外冷凝传热系数分别达到同热通量下光管的11倍与19倍以上;HFC134a工质对应最佳二维肋管的肋密度在1069~1575fpm(肋每米)之间、肋高在0.7~1.5 mm之间,对应最优三维肋管(与本文试验肋型相似)肋密度低于2000fpm;既有二维肋管膜状凝结换热模型需要进一步完善,肋管结构优化过程中应遵循优先提升肋密度的原则。

关键词: 凝结, 传热, 膜, 模型, 强化管, HFC134a, 水平管

Abstract: Design of shell-tube condenser with finned tubes with two dimensional (2D) or three dimensional (3D) fins for HFC134a needs reliable models for the film condensation, which is usually based on reliable experimental data. A new test facility was established to investigate experimentally film condensation characteristics of HFC134a on six enhanced tubes (four kinds of 2D finned tubes and two kinds of 3D finned tubes) and the reliability of existing models and the effect of fin density and fin height on film condensation of HFC134a were discussed. Equivalent outside diameter and active length of test tubes are 19.05 and 1000 mm, respectively. In the experiment, water-side convection heat transfer coefficient for all test tubes is determined by the modified Wilson plot method. The results are as follows. Condensation heat transfer coefficient (CHTC) of HFC134a on single smooth tube is a little higher (5%—8%) than that predicted by the Nusselt model; CHTC of the best 2D (or 3D) finned tubes is 11.5 (or 19) times higher than that of single smooth tube under the same heat flux; the best fin density and fin height of 2D finned tubes are in the regions of 1069—1575 fins per meter (fpm) and 0.7—1.5 mm, respectively; the best fin density of the 3D finned tubes is less than 2000 fpm; the deviations between existing models and experimental results are not acceptable, due to their bad stability or poor accuracy. More work should be done to improve the models for film condensation of HFC134a on 2D finned tubes and develop models for that on 3D finned tubes in the future. The result can be used to guide the design of shell-tube condenser with HFC134a.

Key words: condensation, heat transfer, film, model, enhanced tube, HFC134a, horizontal tube

中图分类号: