化工学报 ›› 2020, Vol. 71 ›› Issue (S1): 430-435.DOI: 10.11949/0438-1157.20191111

• 能源和环境工程 • 上一篇    下一篇

土壤源热泵供暖间歇运行时间的计算分析

王刚(),赵琰   

  1. 河北科技大学建筑工程学院,河北 石家庄 050018
  • 收稿日期:2019-10-07 修回日期:2019-11-14 出版日期:2020-04-25 发布日期:2020-04-25
  • 通讯作者: 王刚
  • 作者简介:王刚(1978—),男,硕士,讲师,wanggang978@163.com
  • 基金资助:
    河北省自然科学基金面上项目(E2019208191)

Calculation and analysis of soil source heat pumps intermittent heating operation time

Gang WANG(),Yan ZHAO   

  1. College of Architecture Engineering, Hebei University of Science and Technology, Shijiazhuang 050018, Hebei, China
  • Received:2019-10-07 Revised:2019-11-14 Online:2020-04-25 Published:2020-04-25
  • Contact: Gang WANG

摘要:

为了充分利用土壤热能,对热泵供热量、运行时间与系统性能之间的关系进行研究。通过对采暖房间建立逐时热平衡方程,推导出房间温度变化与时间关系的计算式。通过该式计算出不同情况下室内平均温度、热泵运行时间、停机时间、供热运行份额的数值,对5种运行方案进行模拟计算分析。结论如下:地下盘管长度设计计算中供热运行份额应根据热泵机组制热量计算得出。热泵制热量相同时时间周期(一次运行时间与停机时间之和)小,运行时间短,地下盘管出口平均水温高,热泵运行效率高,但是随着时间周期变小,室内平均温度下降,热舒适性降低。时间周期相同时热泵制热量越大,运行时间越短,地下盘管出口平均水温高,热泵运行效率高。根据这些特点可采用100%设计热负荷的热泵机组+20%~30%设计热负荷的辅助热源的形式进行热源的配置。

关键词: 间歇供热, 土壤源热泵, 供热运行份额, 数值模拟, 设计

Abstract:

In order to make full use of soil heat energy, the relationship between heat supply, running time and system performance was studied. By establishing the hourly heat balance equation of the room, the calculating formula on room temperature change and time was derived. The average indoor temperature, heat pump running time, downtime, and heating running share were calculated by this model, and the simulation calculation and analysis of five operating schemes were carried out.

Conclusion

in the calculation of underground coil length design, the heating running share should be calculated based on the heat pump unit s heat supply. When heat pump heat production is same, the time period (the sum of one running time and downtime) is small, the running time is short, the average water temperature of the underground coil outlet is high, and the heat pump operation efficiency is high, but as the time period becomes smaller, the average indoor temperature decreases, thermal comfort decreases. When the time period is the same, the heat pump unit s heat supply is bigger and the running time is shorter, the average water temperature of the underground coil outlet is higher, and the heat pump unit s efficient is higher. According to these characteristics, the heat source can be allocated in the form of an heat pump unit with a 100% heat load + an auxiliary heat source with 20%-30% heat load.

Key words: intermittent heating, soil source heat pump, heating operation share, numerical simulation, design

中图分类号: