化工学报 ›› 2014, Vol. 65 ›› Issue (z2): 272-279.DOI: 10.3969/j.issn.0438-1157.2014.z2.040

• 能源和环境工程 • 上一篇    下一篇

太阳能溶液再生性能

钱俊飞, 殷勇高, 张小松, 高龙飞, 张友超   

  1. 东南大学能源与环境学院, 能源热转换及其过程测控教育部重点实验室, 江苏 南京 210096
  • 收稿日期:2014-08-26 修回日期:2014-09-05 出版日期:2014-12-30 发布日期:2014-12-30
  • 通讯作者: 殷勇高
  • 基金资助:

    国家自然科学基金项目(51006022)。

Performance of solar liquid desiccant regeneration

QIAN Junfei, YIN Yonggao, ZHANG Xiaosong, GAO Longfei, ZHANG Youchao   

  1. School of Energy and Environment, Key Laboratory of Energy Thermal Conversion and Control of Ministry of Education, Southeast University, Nanjing 210096, Jiangsu, China
  • Received:2014-08-26 Revised:2014-09-05 Online:2014-12-30 Published:2014-12-30
  • Supported by:

    supported by the National Natural Science Foundation of China (51006022).

摘要:

在太阳能溶液再生系统实验平台上,以LiCl水溶液作为再生盐溶液,对太阳能溶液再生过程进行了实验研究,获得了系统重要运行参数对太阳能溶液再生性能的影响。结果显示:空气和溶液质量流量的增加对系统性能的影响相对较大,再生量分别增加了7倍和51.46%。较高的溶液进口温度能够提高再生量及太阳能溶液再生系统能量利用率,但是溶液温度过高会降低系统能量利用率以及增加系统输入的能量大小,溶液浓度的增加不利于再生量的提高,并会降低太阳能集热器集热效率和系统能量利用率,太阳辐射值的增加可以提高集热器集热效率,但会降低系统能量利用率。为后续如何在溶液再生过程中充分利用太阳能以及优化太阳能溶液再生性能提供了实验依据。

关键词: 太阳能集热器, 再生, 传热, 传质, 集热效率, 能量利用率

Abstract:

To investigate the performance of solar liquid desiccant regeneration, experiments in the system of the solar liquid desiccant regeneration using LiCl solution as the liquid desiccant were performed. The effects of the important operating parameters on the performance of the system were analyzed experimentally. The results showed that,the air and solution mass flow rate had a big positive impact on the performance of the system. The regenerated rate and the energy utilization rate of the system were increased with the liquid desiccant regeneration temperature, but the heat collecting efficiency was decreased with the liquid desiccant regeneration temperature. The regenerated rate, the heat collecting efficiency and the energy utilization rate of the system would be reduced if the solution concentration increased. And the heat collecting efficiency increased when the solar radiation increased, the system energy utilization rate reduced on the other hand. In addition, the experimental results provided reliable data for the further analysis about how to make use of solar energy efficiently on solution regeneration process.

Key words: solar collector, regeneration, heat transfer, mass transfer, heat collecting efficiency, energy utilization rate

中图分类号: